Dyj-s antistatic controller

Dyj-s anti - static controller is an automatic control system for testing electrostatic grounding for loading and unloading of petrochemical products. The ground signal is detected by the ground clamp.
没有此类产品
I want to make an inquiry
Product introduction
Technical Parameters
Explosion-proof certificate

Using range

Dyj-s anti - static controller is an automatic control system for testing electrostatic grounding for loading and unloading of petrochemical products. The ground signal is detected by the ground clamp. When the resistance of the electrostatic discharge circuit between the tank car and the ground pile exceeds the specified safety resistance value, the sound and light alarm signal is output for the on-site staff to timely understand the working state of the system, and the switch volume signal is also output for the use of a third party.
 
Especially suitable for liquid petrochemical products with frequent turnover, such as inflammable and explosive, etc., such as:
 
1. Fuel oil loading system (including railway tank car and road tank car);
 
2. Sealed loading of liquid benzene and hydrocarbons;
 
3. Filling system of other chemical products;

 

System composition and functions

The dyj-s type electrostatic controller is mainly composed of main control panel, DSC electrostatic grounding clamp, DG reset panel and grounding wire.

江苏德大石化科技有限公司1. Main control panel

A. Detect the signal of DSC electrostatic ground clamp;
 
B. Drive alarm to issue sound and light alarm signal;
 
C. Output relay switching signal to loading/unloading system such as oil payment;

 

江苏德大石化科技有限公司2. DSC electrostatic ground clamp

A. special cemented carbide top;
 
B. Break the paint and remove the rust to ensure the car body is well grounded;
 
C. With 7 m PU spiral.

 

 

江苏德大石化科技有限公司3. The DG place plate

Test whether the DSC grounding clamp is reset after use as the basis of standby status of the system.

 

 

 

 

江苏德大石化科技有限公司4. The earth wire

A. Introduce static electricity from the car body into the ground to ensure the generation of static electricity equipment Safe ground;
 
B. The standard distribution cable is 3 meters long (length can be customized).
Corresponding parameter set not found, please add it in property template of background
1. The level of explosion-proof: Ex dia Ⅱ T6 Gb B
 
2. Working voltage: DC24V plus or minus 10%/AC220V plus or minus 10%(DC24V is non-polar)
 
3. Working current: <50mA
 
4. Alarm mode: acoustooptic alarm
 
5. Protection level: IP65
 
6. Response time: <1s
 
7. Working temperature: - 40 ℃ ~ + 60 ℃
 
8. Output signal: 2-way relay output, normally open and normally closed
 
9. Interface capacity: 10A,30VDC; 10. A, 250 vac
 
10. Resistance to set alarm value: 55 Ω

 

Field installation diagram of dyj-s antistatic controller

 

江苏德大石化科技有限公司

 

Layout diagram of field installation of dyj-s antistatic controller

Installation instructions:

1. The diameter of cables to between 8 mm ~ 12 mm Φ Φ.
 
2. This sketch is to recommend the installation method, which can be adjusted according to the actual situation if it meets the requirements of explosion protection.

 